GENERAL DATA
System power range (KVA)
10-40; 60-80; 100-120; 160; 200-300; 400-500;
Active power / frame (kW)
10/15/20/30/40; 54/72; 90/108; 144; 180/225/270; 360/450
UPS output rated PF
0.9
Max no of parallel frames
Up to 6 frames
Max system power
Up to 30 modules
Max system power
3000 kW
Wiring
3ph + N + PE
UPS type
Three-phase standalone
Topology
Online double conversion
INPUT
Nominal input voltage
3 x 380/400/415 V + N
Voltage range
340-460 V
Frequency range
45-66 Hz
Current THD at 100% load
< 3%
Power Factor at 100% load
≥ 0.99
OUTPUT
Rated output voltage
(load dependent)
3 x 380/400/415 V + N
Voltage THD (with linear load)
<2% linear load, <3% nonlinear load (EN 62040)
Rated frequency
50/60 Hz
Efficiency
Double conversion
Up to
92.3%
Up to
91.9%
Up to
92.1%
Up to
94.2%
Up to
94.6%
Up to
94.2%
Eco-mode
Up to
98%
Up to
97.9%
Up to
97.9%
Up to
98.4%
Up to
98.5%
Up to
98.7
Communication
User interface
System graphical display (HMI) + LCD panel UPS Module
Communication ports
SNMP; ModBus; potential free contacts slot, potential free contacts
Software
Monitoring and shutdown software available as option